‹ Low Voltage Switchboards
ATS · AMF · Generator switchboards
ATS / AMF panels and generator switchboards
≤ 6300 A · BlokSeT or GCS build
Alongside the drive cabinets, most data-centre orders bundle low-voltage switchboards for the diesel generator plant, UPS input and output cabinets, and quick-plug cabinets that let prefab MEP modules be connected on site without re-terminating. Boards are built on BlokSeT, GCS or MNS frames to the project's short-circuit and form-of-separation spec.
Tested and certified
As per frame: CE on BlokSeT and MNS; CN type tests
Built for
Data centre generator plant, UPS rooms, Prefab MEP modules.
Standards
IEC 61439, GB 7251.
Technical data
| Parameter | Value |
|---|---|
| Generator boards | Output, paralleling and load-bank ATS boards; 16- and 18-set contracts delivered for KTP-D, Johor |
| UPS cabinets | Input, output and bypass cabinets; 3F UPS output boards for Beijing Daxing and Chengdu campuses |
| Quick-plug cabinets | Quick-connect cabinets for prefab power modules; delivered for NTP-J2, NTP-N, KTP-J2, KTP-C1, KTP-H1, KTP-H2, CTP-A/B/C |
| Frame options | BlokSeT (up to 100 kA), GCS (≤ 6300 A), MNS |
| Certificates | As per frame: CE on BlokSeT and MNS; CN type tests |
Standards
- IEC 61439
- GB 7251
Applications
- Data centre generator plant
- UPS rooms
- Prefab MEP modules
Production process
From enquiry to commissioning
- Enquiry and analysisSend a single-line diagram, load list or panel schedule. An engineer confirms voltage, short-circuit level, forms of separation and applicable standards within 24 hours.
- Proposal and drawingsBudgetary quotation in five working days, then general-arrangement drawings, busbar sizing and a bill of materials for approval.
- Order and engineeringApproved drawings release procurement of Schneider, ABB or specified components and sheet-metal programming.
- Fabrication and assemblyLaser cutting, CNC bending, powder coating, busbar processing, primary assembly and secondary wiring in Shaoshan.
- Factory acceptance testDielectric, loop-resistance, insulation, earth-continuity, IP and current-injection tests; customers and consultants welcome to witness.
- Delivery and after-salesExport packing, sea or air freight, commissioning support and a 7×24 service line with Schneider-trained engineers.
Also in low voltage switchboards

CE
Main LV switchboard, withdrawable (MNS technology)
25 mm-modulus C-profile frame with more than 200 standard parts. English-language type-test report available for export tenders.
≤ 4000 APollution 3Seismic 8
Product detail

Motor control centre, fixed and withdrawable
Motor starter, soft-starter and drive sections on GCK, GCS or BlokSeT frames, with withdrawable drawers for maintenance without shutdown.
0.37–250 kWWithdrawable drawersIcw 50–80 kA
Product detail

Motor control centre (MCC), withdrawable
Power distribution centre and motor control centre in one line-up, 380 or 660 V, up to 3150 A, IP40.
380 / 660 V630–3150 AIcw 80 kA
Product detail

Main LV switchboard, withdrawable
Draw-out switchgear for automated plants that need computer interface; bus up to 4000 A, MCC 1000 A, type-tested to 6300 A.
380 / 660 V≤ 4000 AIcw 50 / 80 kA
Product detail
Quote this product
Send the single-line diagram, short-circuit level and panel schedule; a budgetary quotation follows within five working days.