‹ Low Voltage Switchboards
Bus bridge
Low-voltage copper busbar bridge
660 V · 630–5000 A · ΔT ≤ 60 K
Zhenxiang fabricates its own copper busbar on CNC punch-shear and bending machines, and supplies low-voltage bus bridge for connecting transformers, switchboards and line-ups in three-, four- and five-wire systems.

Tested and certified
Type-tested to the standards listed below.
Built for
Transformer to switchboard links, Data centre power rooms, High-rise risers.
Standards
GB 7251, IEC 61439-6.
Technical data
| Parameter | Value |
|---|---|
| Rated voltage / frequency | 660 V / 50 Hz (60 Hz on request) |
| Rated current | 630–5000 A (60 A minimum per spec) |
| Insulation resistance | ≥ 1000 Ω/V phase-to-phase and phase-to-enclosure |
| Dielectric test | 2500 V, 50 Hz, 1 min, no breakdown |
| Short-circuit | Withstands rated short-time and peak currents per national standard |
| Operating margin | Rated current at 110 % rated voltage |
| Temperature rise | ≤ 60 K at contact points under continuous rated current |
| Service conditions | Indoor continuous; -10 to +40 °C; RH ≤ 90 % at 20 °C |
Standards
- GB 7251
- IEC 61439-6
Applications
- Transformer to switchboard links
- Data centre power rooms
- High-rise risers
Production process
From enquiry to commissioning
- Enquiry and analysisSend a single-line diagram, load list or panel schedule. An engineer confirms voltage, short-circuit level, forms of separation and applicable standards within 24 hours.
- Proposal and drawingsBudgetary quotation in five working days, then general-arrangement drawings, busbar sizing and a bill of materials for approval.
- Order and engineeringApproved drawings release procurement of Schneider, ABB or specified components and sheet-metal programming.
- Fabrication and assemblyLaser cutting, CNC bending, powder coating, busbar processing, primary assembly and secondary wiring in Shaoshan.
- Factory acceptance testDielectric, loop-resistance, insulation, earth-continuity, IP and current-injection tests; customers and consultants welcome to witness.
- Delivery and after-salesExport packing, sea or air freight, commissioning support and a 7×24 service line with Schneider-trained engineers.
Also in low voltage switchboards

CE
Main LV switchboard, withdrawable (MNS technology)
25 mm-modulus C-profile frame with more than 200 standard parts. English-language type-test report available for export tenders.
≤ 4000 APollution 3Seismic 8
Product detail

Motor control centre, fixed and withdrawable
Motor starter, soft-starter and drive sections on GCK, GCS or BlokSeT frames, with withdrawable drawers for maintenance without shutdown.
0.37–250 kWWithdrawable drawersIcw 50–80 kA
Product detail

Motor control centre (MCC), withdrawable
Power distribution centre and motor control centre in one line-up, 380 or 660 V, up to 3150 A, IP40.
380 / 660 V630–3150 AIcw 80 kA
Product detail

Main LV switchboard, withdrawable
Draw-out switchgear for automated plants that need computer interface; bus up to 4000 A, MCC 1000 A, type-tested to 6300 A.
380 / 660 V≤ 4000 AIcw 50 / 80 kA
Product detail
Quote this product
Send the single-line diagram, short-circuit level and panel schedule; a budgetary quotation follows within five working days.