‹ Medium Voltage Switchgear

HXGN-12

Indoor SF6 ring main unit, 12 kV

12 kV · 630 A · 20 kA 3 s

HXGN-12 is a compact, metal-enclosed ring main unit with SF6 load-break switches and fuse-switch combinations for 12 kV ring and radial networks. Modular units cover ring, branch and transformer feeders, with transformer protection up to a 125 A fuse rating.

Request a quotation Certificates
HXGN-12 Indoor SF6 ring main unit, 12 kV

Tested and certified

CN type test (HXGN-12/630-25)

Built for

Urban distribution loops, Data centre MV rings, Industrial parks.

Standards

IEC 62271-200, GB 3906.

Technical data

ParameterValue
Rated voltage / frequency12 kV / 50 Hz
Power-frequency withstand, 1 min42 kV; 48 kV across isolating distance
Lightning impulse withstand75 kV; 85 kV across isolating distance
Busbar / max. fuse rating630 A / 125 A
Short-time / peak withstand20 kA 3 s / 50 kA
Operations100 full-load; 2000 mechanical
EnclosureIP3X
CertificatesCN type test (HXGN-12/630-25)

Standards

  • IEC 62271-200
  • GB 3906

Applications

  • Urban distribution loops
  • Data centre MV rings
  • Industrial parks
  • Renewable feeders

Production process

From enquiry to commissioning

  1. Enquiry and analysisSend a single-line diagram, load list or panel schedule. An engineer confirms voltage, short-circuit level, forms of separation and applicable standards within 24 hours.
  2. Proposal and drawingsBudgetary quotation in five working days, then general-arrangement drawings, busbar sizing and a bill of materials for approval.
  3. Order and engineeringApproved drawings release procurement of Schneider, ABB or specified components and sheet-metal programming.
  4. Fabrication and assemblyLaser cutting, CNC bending, powder coating, busbar processing, primary assembly and secondary wiring in Shaoshan.
  5. Factory acceptance testDielectric, loop-resistance, insulation, earth-continuity, IP and current-injection tests; customers and consultants welcome to witness.
  6. Delivery and after-salesExport packing, sea or air freight, commissioning support and a 7×24 service line with Schneider-trained engineers.