‹ Medium Voltage Switchgear

KYN61-40.5

Armoured withdrawable MV switchgear, 40.5 kV

40.5 kV · 1250–2500 A · 31.5 kA

KYN61-40.5 is the 35 kV-class switchgear improved by the factory from the original design. The aluminium-zinc coated body is CNC-formed and bolted or riveted, the cable compartment gives more than 300 mm phase clearance without insulating barriers, and the main bus passes straight through the line-up.

Request a quotation Certificates
KYN61-40.5 Armoured withdrawable MV switchgear, 40.5 kV

Tested and certified

CN type test; XIHARI reports at 1250 and 2500 A / 31.5 kA

Built for

35 kV substations, Energy storage stations, Renewable collector substations.

Standards

GB 11022, GB 3906, GB 1984, DL/T 404, IEC 60694, IEC 62271-100 / -200.

Technical data

ParameterValue
Rated voltage40.5 kV
Rated current1250 / 2500 A (tested at 31.5 kA)
Breaker trucksZN85-40.5, HVX40, VD4, 3AE8, CV2
EnclosureAluminium-zinc coated steel, fully assembled construction
Cable compartmentPhase clearance > 300 mm, no insulation partition required
Service conditions-25 to +40 °C, ≤ 1000 m, RH ≤ 95 % daily
CertificatesCN type test; XIHARI reports at 1250 and 2500 A / 31.5 kA

Standards

  • GB 11022
  • GB 3906
  • GB 1984
  • DL/T 404
  • IEC 60694
  • IEC 62271-100 / -200

Applications

  • 35 kV substations
  • Energy storage stations
  • Renewable collector substations
  • Heavy industry

Production process

From enquiry to commissioning

  1. Enquiry and analysisSend a single-line diagram, load list or panel schedule. An engineer confirms voltage, short-circuit level, forms of separation and applicable standards within 24 hours.
  2. Proposal and drawingsBudgetary quotation in five working days, then general-arrangement drawings, busbar sizing and a bill of materials for approval.
  3. Order and engineeringApproved drawings release procurement of Schneider, ABB or specified components and sheet-metal programming.
  4. Fabrication and assemblyLaser cutting, CNC bending, powder coating, busbar processing, primary assembly and secondary wiring in Shaoshan.
  5. Factory acceptance testDielectric, loop-resistance, insulation, earth-continuity, IP and current-injection tests; customers and consultants welcome to witness.
  6. Delivery and after-salesExport packing, sea or air freight, commissioning support and a 7×24 service line with Schneider-trained engineers.

Quote this product

Send the single-line diagram, short-circuit level and panel schedule; a budgetary quotation follows within five working days.

Request a quotation